SOLUTIONS / DATA CENTER POWER SMOOTHING

Data center power smoothing for AI loads.

AI training moves tens of megawatts in under a second, every 20 seconds or so, thousands of times a day. A battery on the block takes every pulse and the grid draw stays flat. The simulations below run the production control code on a training load shape digitized from a published figure of a GPU training cluster.

01 / THE LOAD PULSE

Each training step swings the campus by about 500 MW.

A GPU cluster training a model runs the same cycle over and over: compute, synchronize, compute. Power rises to the cluster’s peak during compute and falls during synchronization. When one job spans a 1 GW campus, the swing is about 500 MW, and it repeats every 20 seconds or so, with shorter dips in between. Utilities see this as flicker, voltage instability and a power oscillation they will not accept at the point of interconnection without mitigation.

A 1 GW campus running one training job, one hour at 1 ms. The grey band is the range of the load in each second, down to about 430 MW at every step. The navy line is the grid draw with the UPS blocks, which stays between 805 and 815 MW.
ENERGENCE / POWER SMOOTHING, ONE HOURA 1 GW campus running one training job, one hour at 1 ms. The grey band is the range of the load in each second, down to about 430 MW at every step. The navy line is the grid draw with the UPS blocks, which stays between 805 and 815 MW.

02 / ZOOMED IN

Twenty seconds, every sample.

Zoomed to twenty seconds, the training cycle is visible as a square-edged pulse with sub-second texture. The battery discharges on the rise and charges on the fall, so the sum of load and battery seen by the grid is a flat line. In the dual-conversion topology the load-side converter serves the load as a voltage source, so the pulse never passes through a control loop. A small residual remains at the point of interconnection, 5.7 MW filtered in the 1 GW case, which is why parallel blocks at a 3 ms response read the same. In the parallel topology the blocks sit beside the load and inject the opposite of each pulse through a control loop. The simulation gives that loop a 3 ms total response, from measurement through command to the converter.

Twenty seconds inside the hour at 1 ms. Top: training load in grey, grid draw in navy. Bottom: battery power, orange when discharging and blue when charging, up to about 380 MW as the campus drops to the floor of each step.
ENERGENCE / POWER SMOOTHING, TWENTY SECONDSTwenty seconds inside the hour at 1 ms. Top: training load in grey, grid draw in navy. Bottom: battery power, orange when discharging and blue when charging, up to about 380 MW as the campus drops to the floor of each step.

ENERGENCE / POWER SMOOTHING, LIVEThe same run played in real time as a rolling twelve-second window. The load pulses, the battery mirrors them, and the grid draw stays flat.

03 / POWER VARIATION

ERCOT's proposed 10 MW in 5 seconds, simulated.

ERCOT has proposed a power-variation limit for large loads: the peak-to-peak change in active power, filtered to 0.1 to 55 Hz, may not exceed 10 MW in any rolling 5-second window. The proposal was presented to the Large Load Working Group in February, April and June 2026. We run the production control algorithm against it at two scales, with the training load shape digitized from a published figure of a GPU training cluster, scaled to each site.

A 120 MW AI hall over one hour at 1 ms resolution. The load swings 49 MW in 5 seconds on the filtered metric. The grid draw with the UPS block reads 0.24 MW filtered and 0.31 MW raw, against a 10 MW limit enforced at 85 %.
ENERGENCE / ERCOT POWER VARIATION, 120 MW HALLA 120 MW AI hall over one hour at 1 ms resolution. The load swings 49 MW in 5 seconds on the filtered metric. The grid draw with the UPS block reads 0.24 MW filtered and 0.31 MW raw, against a 10 MW limit enforced at 85 %.

One training job across a 1 GW campus with 50 ms of timing spread, the case where the whole campus moves together. The load swings from 424 to 971 MW. The grid draw with the UPS blocks stays between 805 and 815 MW and reads 5.7 MW filtered and 6.6 MW raw over two hours, against the same 10 MW limit.
ENERGENCE / ERCOT POWER VARIATION, 1 GW CAMPUS, ONE TRAINING JOBOne training job across a 1 GW campus with 50 ms of timing spread, the case where the whole campus moves together. The load swings from 424 to 971 MW. The grid draw with the UPS blocks stays between 805 and 815 MW and reads 5.7 MW filtered and 6.6 MW raw over two hours, against the same 10 MW limit.

Parallel blocks give the same reading. In the same 1 GW case the grid draw with parallel blocks, at a 3 ms total response, reads 5.7 MW filtered and 6.6 MW raw against the same 10 MW limit.

Basis: the training load shape is digitized from a published figure of a GPU training cluster (Choukse et al., arXiv 2508.14318, 2025) and interpolated to 1 ms for the simulation. It is scaled to a 120 MW hall of four independent jobs with 100 ms of timing spread, and to a 1 GW campus (600 MW of IT, 400 MW of cooling and mechanical load) running one job with 50 ms of spread. In the charts each block is a dual-conversion medium-voltage UPS sized to the load, 2 hours of energy, 70 % state-of-charge target. The parallel reading uses the same 1 GW case with a 3 ms total response. The campus reading is taken over the last two hours of a three-hour run, after start-up. The filter corners at 0.033 Hz and 165 Hz are our assumption, since the proposal does not prescribe the filter. The raw reading, without the filter, is shown as the conservative bound. The rule had not been filed as a protocol revision at the time of writing.

04 / GENERATOR PROTECTION

Pulses that generators cannot follow.

AI load pulses put torsional stress on the shafts of reciprocating engines and gas turbines, and no generator can follow a load that moves 500 MW within a second. A site that runs AI load with behind-the-meter generation, even with a partial grid connection, needs the battery to take the pulses so the generators see a smooth load. Fuel cells and small modular reactors ramp more slowly still, and the battery takes the fast part of the change.

Where the generators connect decides which ones the battery protects. Parallel blocks protect generation that shares their medium-voltage bus: on-site prime generation, or medium-voltage standby generators. Low-voltage standby generators behind a hall’s own transfer switch are outside the blocks’ path once the hall transfers. With dual conversion, generation upstream of the blocks sees the grid-side converters’ slow average.

The same control also damps power oscillations between the load and the supply, with configurable settings for flicker mitigation and oscillation prevention. The data center interconnection page covers ramp rate control and on-site generation. Request information with your load profile and its time resolution to see your site simulated.

YOUR PROJECT

Request information

Tell us what you are evaluating. An engineer will review your request.

Use your company domain. Personal email providers are not accepted.

By submitting, you agree that Battalion may contact you about this request.